MBS100W ( WI-FI – MODBUS Gateway)

FMT Mühendislik > MODBUS GATEWAY > MBS100W ( WI-FI – MODBUS Gateway)

MBS100W ( WI-FI - MODBUS Gateway)

FEATURES
APPLICATIONS
DRAWINGS
PRODUCT CODE
DOWNLOADS

Product Features

User-friendly Software for Configuring Gateway

Yes

Programming with USB Cable

Yes

Upload/Download Program over TCP/IP

Yes

Master/Slave Communication

Yes

Communication Between Networks Through Protocols

Yes

Multiple Connectivity

Yes

Auto-Detect Socket Disconnection and Auto-Reconnection

Yes

Remote Firmware Upgrade

Yes

View Status of Device Over Web-Interface

Yes

Programming

Programming Editor

Assistant Software

Device Search over Network

Yes

Offline Configuration

Yes

Import/Export Configuration

Yes

Integrated Communication Ports

Wi-Fi

1 Port, IEEE 802.11 b/g/n

Serial Ports

1 Port RS485 (3 kV ESD Protection), 1 Port RS232

 

or 2 Port RS485

USB

1 Port, Mini USB Type B

Communication Protocols

Master Communication Protocols

MODBUS RTU, MODBUS TCP

Slave Communication Protocols

MODBUS RTU, MODBUS TCP

Communication Modes

Between MODBUS TCP Master and MODBUS RTU Slave

Yes

Between MODBUS RTU Master and MODBUS TCP Slave

Yes

MODBUS RTU Over TCP

Yes

Maximum Connection Count

Number of Server Socket

2

Number of Client Sockets per TCP Server Socket

16

Number of Slave Device on RS485

247

LED Signals

Power

1 LED Blue

Running Status

1 LED Blue

Error

1 LED Blue

Environmental Conditions

Operating Temperature

-20 / +75 C

Storing Temperature

-40 / +80 C

Humidity

5..95 RH

Protection Standard

IP20

Operating Altitude

0..2000 m

Electrical Wiring

Serial Port Inputs

Demountable Terminal Block with Screw, (pitch 3.81 mm)

Power Supply Input

Demountable Terminal Block with Screw, (pitch 3.81 mm)

Supply

Supply Voltage

9..36 VDC

Supply Current

50 mA @ 24 VDC

Warranty

Duration

24 Months

Certificates

CE

Applications

  Monitoring Energy Analysers

  Monitoring Power Protection Relays

  Compensation Tracking Systems

  Temperature Control Applications

  Remote Monitoring of Cooling Tanks

  Energy Tracking and Billing Systems

Telemetry

  Master Protocols: MODBUS RTU, MODBUS TCP

  Slave Protocols: MODBUS RTU, MODBUS TCP

  MODBUS RTU over TCP Mode

 

Product Code

GSM/Ethernet/WI-FI

RS232

RS485

USB

 

MBS100W

WI-FI

1

1

1

 

MBS101W

WI-FI

.

2

1

 

 

Tıkla Ara